Program buttons – RKI Instruments Beacon 200 User Manual

Page 11

Advertising
background image

Internal Description • 11

Status Lights

The Beacon 200 includes four status lights that indicate the current status
of the monitor. The status lights are to the left and right of the display (see
Figure 2).

Pilot Light. The pilot light is on when the Beacon 200 is receiving
incoming power.

Fail Light. The fail light turns on when the Beacon 200 is experiencing
a fail condition. A fail condition can be caused by a failure within the
Beacon 200 or detector head(s) wired to the Beacon 200. See Chapter
5, Maintenance, or the troubleshooting section in the applicable
detector head manual to respond to a fail condition.

Alarm 1 Light. The alarm 1 light is on when the Beacon 200 is
experiencing an alarm 1 gas condition.

Alarm 2 Light. The alarm 2 light is on when the Beacon 200 is
experiencing an alarm 2 gas condition.

Program Buttons

The Beacon 200 includes four program buttons that allow you to enter the
instrument programs, navigate through the programs, update instrument
and channel settings, and save changes to the program settings. When a
program button is pressed, a buzzer located on the display PCB beeps.
The program buttons are near the right edge of the display PCB (see
Figure 2).

Table 2: Beacon 200 Program Button Functions

Button

Function

ESCAPE

Moves backward through the program menus

Cancels changes you make in the program menus

Enters the Channel Control and Setup program (press with the ENTER button)

UP/YES

Accepts the displayed setting and proceeds to the next setting

Changes the displayed setting

Enters the Calibration program (press with the ENTER button)

DOWN/NO

Allows you to update the displayed setting

Changes the displayed setting

ENTER

Saves changes you make in the programs

Enters the Channel Control and Setup program (press with ESCAPE button)

Enters the Calibration program (press with the UP/YES button)

Enters the Input Setup Program (press while flipping power switch to ON position)

Advertising