Wiring the Beacon 200 Gas Monitor • 25

6. Connect the wires from the transmitter to the appropriate detector/

transmitter terminals. The top detector terminal strip is for channel 1
and the bottom one is for channel 2. See the transmitter instruction
manual for controller terminal connections. Figure 10 below illustrates
typical transmitter wiring connections.

CAUTION: Do not route power and transmitter wiring through the same

conduit hub. The power wiring may disrupt the transmission of
the transmitter’s signal to the Beacon 200.

AMP/PREAMP

OXYGEN

+

+ S

LEL

R

W

G

B

2-Wire 4-20 ma
Transmitter

+ 24 VDC

FB (4-20 mA)

OXYGEN

2-Wire Connection

+ S

AMP/PREAMP

+

3-Wire 4-20 ma
Transmitter

3-Wire Connection

+ 24 VDC

FB (4-20 mA)

- (DC GROUND)

LEL

R

W

G

B

Figure 10. Generic 4 to 20 mA Transmitter Output Wiring