RKI Instruments Beacon 200 Rig Monitor, LEL/LEL User Manual

Page 29

Advertising
background image

Beacon 200 Rig Monitor Operator’s Manual • 24

Alarm 2 Condition

This section describes the audible and visual indications for an alarm 2
condition and suggests response to an alarm 2 condition.

Alarm 2 Condition Indications

When the gas reading of an active channel reaches the alarm 2 setpoint,
the Rig Monitor senses an alarm 2 condition. The Rig Monitor alerts you to
an alarm 2 condition as follows:

The ALARM 2 light turns on.

The gas reading in alarm 2 condition continues to flash and alternates
with the ALARM-2 messages.

The buzzer sounds a Pulsing tone.

The common alarm 2 relay energizes.

The applicable alarm 2 channel relay energizes.

Responding to an Alarm 2 Condition

This section suggests response to an alarm 2 condition.

1. Follow your established procedure for a high level combustible gas

condition.

2. Alarms are latching. After the gas reading falls below the alarm 2

setpoint, press the reset switch to reset the alarm circuit. Resetting the
alarm circuit turns off the ALARM 2 light, and de-energizes the common
and channel alarm 2 relays.

NOTE: To silence the buzzer while in an alarm 2 condition, press the

reset switch.

You cannot de-energize the alarm 2 relays until the gas reading
falls below the alarm 2 setpoint.

Fail Condition

This section describes the audible and visual indications for a fail condition
and suggests response to a fail condition.

Fail Condition Indications

The Rig Monitor senses a fail condition for any of the following:

The detector head wiring to the Rig Monitor is disconnected or
incorrectly connected.

The detector head’s detector is disconnected or incorrectly connected.

Advertising