25 • Beacon 200 Rig Monitor Operator’s Manual

The display reading is -10% of full scale or lower.

The Rig Monitor or detector head is malfunctioning.

When the Rig Monitor senses a fail condition, it alerts you as follows:

The FAIL light turns on.

The gas reading for the failing channel is replaced by the FAIL
message.

The buzzer sounds a steady tone.

The common fail relay de-energizes.

NOTE: If you elected to use the channel’s alarm 2 relay as an individual

fail relay in the Channel Control & Setup menu, the relay de-
energizes in a fail condition. See “Chapter 5: Channel Control and
Setup Program” on page 27 for a description of this setting.

Responding to a Fail Condition

This section suggests response to a fail condition.

1. Verify that the detector head wiring to the Rig Monitor is correctly and

securely connected.

2. Verify that the detector head’s detector is correctly and securely

connected.

3. See the troubleshooting guide in the detector head instruction manual.

Low Battery Condition

The 12 VDC battery that is recommended for operation of the Rig Monitor
is typically dead before the power converter recognizes a low power
condition. As a result, when the Rig Monitor is used with a 12 VDC battery,
there may be no low power alarm and the unit will instead shut off once the
battery is dead.