M2A Transmitter Operator’s Manual

28

Alarm Indications

NOTE:

The M2A includes alarm on and alarm off delay settings for alarm 1 and alarm 2. The
alarm indications described in this section operate according to the factory set alarm
settings. See Table 6 on page 32 for all the factory settings.

NOTE:

You can select normally energized (N. EN) or normally de-energized (N. DE-EN)
alarm 1 and alarm 2 relay settings in Configuration Mode. The following sections
describe the standard factory setting for these relays which is N. DE-EN.

The fail relay is factory set as N. EN and is not user-adjustable.

Alarm 1 Condition

Alarm 1 Condition Indications

When the gas reading reaches the alarm 1 setpoint, the M2A senses an alarm 1 condition. The M2A
alerts you to an alarm 1 condition as follows:

The A1 LED turns on.

The gas reading alternates with the ALARM-1 message.

The alarm 1 relay energizes.

Responding to an Alarm 1 Condition

1.

Follow your established procedure for a low level combustible or toxic gas condition or a
decreasing oxygen concentration condition.

2.

After the gas reading falls below (above for oxygen) the alarm 1 setpoint, press the ENTER
button to reset the alarm 1 circuit. Resetting the alarm 1 circuit turns off the A1 LED, resets the

Table 5: Visual and Audible Alarm Indications

Condition

Cause

Visual Indication(s)

Alarm 1

1

Increasing (decreasing for O

2

) gas reading at

or above the alarm 1 setpoint

A1 LED is on

Gas reading alternates with
ALARM-1 message

Alarm 2

1

Increasing gas reading at or above the alarm 2
setpoint

A2 LED is on

Gas reading alternates with
ALARM-2 message

Fail

Disconnected or misconnected detector
wiring

Display reading at -10% of full scale or
lower

Defective components

F LED is on

FAIL message replaces gas
reading

NOTE: There is a 30 second delay
on the fail condition.

Low Power

DC power source less than 9.5 volts.

F LED is on

LowPower message and actual
voltage of incoming DC power

*

1

If the M2A is in both an alarm 1 and an alarm 2 condition, both alarm LEDs are on and the

display alternates between the gas reading and the ALMS 1&2 message.