Recommended modbus wiring, Alternate modbus wiring for existing installations, M2a transmitter operator’s manual 52 – RKI Instruments M2A User Manual

Page 57

Advertising
background image

M2A Transmitter Operator’s Manual

52

Recommended Modbus Wiring

The recommended Modbus wiring for the M2A is illustrated in Figure 27 below. In this
configuration, 5 wires are used for wiring the M2A into a Modbus system. Figure 27 also illustrates
typical alarm device wiring. The ground jumper must be removed in this wiring configuration.

Figure 27: Recommended Modbus Wiring

Adding an M2A to an Existing M2 Modbus Installation with Recommended Wiring

An M2A can be wired into an existing M2 Modbus system. The shape of the terminal PCB will be
different but the wiring connections are identical and the ground jumper on the M2A must still be
removed.

Alternate Modbus Wiring For Existing Installations

Although the wiring shown in Figure 27 is recommended, it is possible to wire the M2A into a
Modbus system with only 4 wires in situations where a pre-existing system is being replaced and
wiring is already in place. This should only be done if wiring for a system that is being replaced is
already installed and it is not practical to run another wire. See Figure 28 below for this wiring
configuration. In this configuration, the wire between the “C” terminal on the M2A and the
Common terminal on the Modbus controller is omitted. Instead, the Common terminal on the
Modbus controller is connected to the “-” of the 24 VDC power supply. The ground jumper must be
installed in this wiring configuration.

Figure 28: Alternate Modbus Wiring

Power Supply

Remove Ground Jumper

10-30 VDC

-

+

Modbus Controller

Input

Terminals

D0

D1

Common

To

Additional

M2As

C

NC

NO

AL

AR

M

1

C

N

C

N

O

AL

A

R

M

2

C

N

C

N

O

FA

IL

See

Detect or

W iring

-

S

+

A

B

C

R

S

485

PW

R

/S

IG

R

W

G

B

LE

L

-

S

+

A

B

C

R

S

485

PW

R

/S

IG

R

W

G

B

LE

L

C

NC

NO

AL

AR

M

1

C

N

C

N

O

AL

A

R

M

2

C

N

C

N

O

FA

IL

See

Detect or

W iring

+

-

10-30 V DC

Power Supply

Input

Terminals

Modbus Controller

D1

Common

D0

C

N

C

N

O

AL

AR

M

1

C

N

C

N

O

AL

AR

M

2

C

N

C

N

O

FA

IL

-

S

+

A

B

C

RS

4

8

5

PW

R

/SI

G

R

W

G

B

LE

L

-

S

+

A

B

C

RS

4

8

5

PW

R

/SI

G

R

W

G

B

LE

L

See

Detect or

W iring

C

N

C

N

O

AL

AR

M

1

C

N

C

N

O

AL

AR

M

2

C

N

C

N

O

FA

IL

To

Additional

M2As

See

Detect or

W iring

Advertising