Using the M2A in a 4-wire Modbus System

Although the M2A is a 2-wire Modbus RTU device, it can be used with a 4-wire Modbus controller
if the system wiring is modified as follows:

Connect the controller’s TxD0 and RxD0 wires together and use this connection as the 2-wire
Modbus D0 signal.

Connect the controller’s TxD1 and RxD1 wires together and use this connection as the 2-wire
Modbus D1 signal.

Connect these D0 and D1 signals and the common wire from the controller to the 2-wire
Modbus Network of M2As.

Modbus Mode

Modbus Mode allows you to configure various parameters relating to the Modbus setup of the
M2A. Modbus Mode includes a 5-minute time-out feature. If you do not press a control button for
5 minutes, the M2A automatically returns to normal operation.

NOTE:

If the M2A returns to normal operation because of a time-out, it enters a warm-up
period just as it does when it is first turned on.

1.

While in normal operation, simultaneously press and hold the DOWN/NO and ENTER buttons

ID = 128

RS-485

M2A

Termination

Jumper

Installed

Modbus

Master

Up to 128 M2As can be connected without a repeater

M2A

Termination

Jumper

Not Installed

M2A

Termination

Jumper

Not Installed

M2A

Termination

Jumper

Not Installed

M2A

Termination

Jumper

Not Installed

ID = 2

ID = 3

RS-485

ID = 1

M2A

Termination

Jumper

Installed

ID = 127

ID = 4