SATEC ETC2002 User Manual

Page 46

Advertising
background image

Chapter 5 Setting Up the ETC2002

Configuring Data Server

46

ETC2002 Network Communicator

Data Server Options

To view the Data server options, type i and press Enter.

Data server>i

Data Server Configuration

------------------------------------

Data server disabled

Continuous polling disabled

Polling interval 1 min

Logging interval 1 (x1min)

To setup or change the Data server options, type p and press Enter. To
change an option, type your new setting after the prompt and press Enter. To
leave the setting unchanged, just press Enter. Refer to the table below for
the available options and their explanation.

Data server>p

Data server: disabled

New [y/n]:

Continuous polling: disabled

New [y/n]:

Polling interval: 1 min

New:

Logging interval: 1 (in polling interval units)

New:

Data Server Exchanges

See

Data Server

in Chapter 3 for more information on using Data server

exchanges.

To inspect the present configuration (to leave the settings unchanged, just
press Enter) or configure the Data server exchanges:

1. Type

s

and press Enter. The following prompt appears:

Data server>s

Data Exchange No:

2. Type the data exchange number, and then specify the device address,

the start device register and the number of registers in the real-time data
exchange. Note that the real-time, status event and write data

exchanges with the same exchange number are internally linked in the
ETC2002 to the same device address.

Device ID: 1

New:

Start device register address: 256

New:

Number of registers: 1

New:

3. Enable real-time polling for the exchange if you want to start exchange

operations:

Polling: enabled

New [y/n]:

4. Enable updating the real-time clock in the device if you wish to

periodically synchronize its clock with the ETC2002 clock:

RTC update: disabled

New [y/n]:

Advertising