Chapter 5 Setting Up the ETC2002

Configuring Data Server

ETC2002 Network Communicator

49

See

Data Server

in Chapter 3 for more information on using real-time data

exchanges. Refer to the ETC2002 Modbus Guide for information on how to
access the acquired real-time and logged data via communications.

The following table lists available options.

Parameter Options

Default Description

Device Address

1-247

1

Defines the device to which
the exchange is linked

Device Start Register

0-65535

0

Defines the start device
register for real-time
polling

Block Size

1-114

0

Defines the number of

contiguous registers in the
exchange

Polling Enabled

Disabled,
Enabled

Disabled

Enables polling the device

RTC Sync Enabled

Disabled,

Enabled

Disabled

If enabled, the Data server

synchronizes the device
clock with the ETC2002
clock

To configure a real-time data exchange:

1. Define the device address for a data exchange. Note that

the real-time, status event and write data exchanges with
the same exchange number are internally linked in the

ETC2002 to the same device address.

2. Specify the start register address of the area in the device

Modbus map you wish to be polled via the exchange.

3. Type the number of registers in the exchange. Up to 114

registers can be specified for a single exchange. As you

type the register address range, PAS immediately shows
you the start register address in the ETC2002 exchange
area for accessing the acquired data from the remote
applications.

4. Check the “Polling Enabled” box to activate the exchange.