Chapter 5 Setting Up the ETC2002

Configuring Data Server

50

ETC2002 Network Communicator

Status Event Exchanges

To enter the Setup dialog, select the ETC2002 site from the list box on the
PAS toolbar, select ETC2002 Setup from the Meter Setup menu, and then
click on the Status Event Exchanges tab.

See

Data Server

in Chapter 3 for more information on using status event

exchanges. Refer to the ETC2002 Modbus Guide for information on how to
access the event log data via communications.

The following table lists available options.

Parameter Options

Default Description

Device address

1-247

1

Defines the device to which
the exchange is linked

Register Address

0-65535

0

Defines the device status
event register address for
polling

Event Mask

0-0xFFFF

0

Defines the bit mask for

bits which status must be
checked for events

Polling Enabled

Disabled,
Enabled

Disabled

Enables polling the status
register

Auto Reset

Disabled,

Enabled

Disabled

If enabled, the Data server

clears the device register
after it has been read

To configure a status event exchange:

1. Define the device address for a status event exchange.

Note that the real-time, status event and write data
exchanges with the same exchange number are internally

linked in the ETC2002 to the same device address.

2. Specify the device status register address you wish to be

polled via the exchange.

3. Specify the event mask for bits you wish to be checked for

events.

4. Check the “Polling Enabled” box to activate the exchange.

Advertising