Example
Chosen measuring range:

-50 ... +150 °C

Set minimum temperature (-50 °C)
on the PT 100 simulator and calibrate the signal conditioner out-
put signal to 4.000 mA using the null potentiometer .
Mean temperatur e

= (

ϑ

max

+

ϑ

min

)/2

= (150 °C + (-50 °C))/2
= 50 °C

Set the 50 °C value on the PT 100 simulator
Then determine

I:

I = measured value from measuring

instrument - 12.000 mA

I = 11.940 mA - 12.000 mA

= -0.060 mA

Then calibrate the output signal to (12.000 mA -

I) using the

span potentiometer i.e. her e an example.

"12.000 mA - (-0.060 mA) = 12.060 mA"

Then set the maximum temperature on the PT 100 simulator and
calibrate the output signal to 20.000 mA using the lin potentiome-
ter.