22

3.4 Pluggable cross-connections for voltage supply

(Figure 4)

A maximum feed through of 2 A is possible.
If a signal conditioner is accidently rotated thr ough 180°, the
cross-connection cannot be inserted.

3.5 Labelling possibilities

Figur e 5

WS 10 connector markers can be used to label module.

4

Calibration

Warning!!

The power supply must be disconnected, before

changing the signal conditioner settings using the DIP
switches.
Failur e to observe will lead to considerable damage!

4.1 Equipment

Power supply 24 Vdc, 50 mA

Simulator for PT 100 or precision r esistance decade

Current meter/voltmeter that can be so calibrated, as to allow

an accuracy of > 0.1 % fr om the upper range value