Weidmuller PT 100/4 signal conditioners for current output User Manual

Page 7

Advertising
background image

25

4.3 Linearity calibration
1.

Proceed with basic calibration, see above.

2.

Add 1 % of the temperature span to the selected " minimum"
temperature and set this value on a PT 100 simulator (when
using a precision r esistance decade, where necessary ob-
serve DIN IEC 751 conversion table from °C to

!) and cali-

brate the signal conditioner output signal to 0.200 mA using
the null potentiometer .

3.

Set the mean temperatur e "(

ϑ

max

+

ϑ

min

)/2" on a PT 100 simu-

lator.
Determine the difference to the desired value:
"

I = shown value on measuring instrument - 10.000 mA"

and calibrate the output signal to (10.000 mA -

I) using the

span potentiometer .

4.

Set the " maximum" selected temperatur e

ϑ

max

on a PT 100

simulator and calibrate the signal output to 20.000 mA using
the lin potentiometer .

5.

Repeat steps 2 to 4 until the required accuracy is achieved.