26

Example
Chosen measurement -50 ... +150 °C →

200 K span

range:

1 % fr om 200 K span = 2 K

Set minimum temperature -50 °C + 2 K = -48 °C
on the PT 100 simulator and calibrate the signal conditioner out-
put signal to 0.200 mA using the null potentiometer .
Mean temperatur e

= (

ϑ

max

+

ϑ

min

)/2

= (150 °C + (-50 °C))/2
= 50 °C

Set the 50 °C value on a PT 100 simulator
Then determine

I:

I = measured value from measuring

instrument - 10.000 mA

I = 9.940 mA - 10.000 mA

= -0.060 mA

Then calibrate the output signal to (10.000 mA -

I) using the

span potentiometer i.e. her e an example.

"10.000 mA - (-0.060 mA) = 10.060 mA"

Then set the maximum temperature on the PT 100 simulator
(150 °C) and calibrate the output signal to 20.000 mA using the
lin potentiometer .