Step 6: install the new scr modules – Rockwell Automation 20P PowerFlex DC Drive - Frame B SCR Modules User Manual

Page 17

Advertising
background image

PowerFlex® DC Drive - Frame B SCR Modules

17

Step 6: Install the New
SCR Modules

Install the new SCR Modules in reverse order of removal as detailed in Step
5:

Remove the Existing SCR Modules on page 11

.

Important Notes for installation:

Thermal grease must be applied to the bottom of each SCR Module
before securing it to the heatsink.

Use the following table to determine the proper tightening torque for the
SCR Modules installed on the heatsink:

Use the following orientation for installing the SCR Modules:

Use the following table to determine the proper tightening torque for the
bus bars connected to the SCR Modules:

230V AC Input

460V AC Input

Part Number

Final Torque

Part Number

Final Torque

SK-20P-S7F48 2.5…4 N•m (22…35.4 lb•in)

SK-20P-S7F78 2.5…4 N•m (22…35.4 lb•in)

SK-20P-S7F49 4.5…5.5 N•m (40…48.7 lb•in)

SK-20P-S7F79 4.5…5.5 N•m (40…48.7 lb•in)

SK-20P-S7F42 4.5…5.5 N•m (40…48.7 lb•in)

SK-20P-S7F41 4.5…5.5 N•m (40…48.7 lb•in)

SK-20P-S727F 4.5…5.5 N•m (40…48.7 lb•in)

SK-20P-S737F 4.5…5.5 N•m (40…48.7 lb•in)

230V AC Input

460V AC Input

Part Number

Final Torque

Part Number

Final Torque

SK-20P-S7F48 4.5…5.5 N•m (40…48.7 lb•in)

SK-20P-S7F78 4.5…5.5 N•m (40…48.7 lb•in)

SK-20P-S7F49 4.5…5.5 N•m (40…48.7 lb•in)

SK-20P-S7F79 4.5…5.5 N•m (40…48.7 lb•in)

SK-20P-S7F42 11…13 N•m (97.4…115 lb•in)

SK-20P-S7F41 11…13 N•m (97.4…115 lb•in)

SK-20P-S727F 11…13 N•m (97.4…115 lb•in)

SK-20P-S737F 11…13 N•m (97.4…115 lb•in)

1

2

3

2

1

3

Gate leads at top

Gate leads at bottom

This SCR Module
only present in
regenerative drives.