Rockwell Automation 20P PowerFlex DC Drive - Frame B SCR Modules User Manual

Page 5

Advertising
background image

PowerFlex® DC Drive - Frame B SCR Modules

5

Step 4: Remove the Pulse
Transformer and Switching
Power Supply Boards

Note: The Switching Power Supply circuit board is located on the back of
the Pulse Transformer circuit board. You do NOT need to remove the
Switching Power Supply board from the back of the Pulse Transformer
board.

1. Remove the plug-in terminal from the field input block at the top of the

drive.

2. Remove the four screws that secure the slotted air flow plate to the top

of the drive chassis.

Important: The air flow plate is also secured to the Pulse Transformer

circuit board and therefore cannot yet be removed.
Instructions for doing so are included later in this
procedure.

Air flow plate

Remove screws

Remove
plug-in
terminal

Front of Drive

Advertising