PowerFlex® DC Drive - Frame B SCR Modules

Note the proper order of the washers when installing the bolts connecting
the bus bars to the SCR Modules and other bus bars.

For Regenerative drives, the longer leg of the intermediate AC input bus
bars connect to the top of the SCR Modules:

For Regenerative drives, five of the bolts are 24mm long and the rest are
20mm long. For non-regenerative drives, two of the bolts are 24 mm long
and the rest are 20 mm long. Install the 24mm bolts in the following
locations:

Bolt

Lock washer

Flat washer

Intermediate
bus bar

Phase U, V, or
W bus bar

SCR Module
on heatsink

Top of Drive

Long leg

Short leg

24mm bolt locations

Regenerative Drive Shown