Powerflex 700s, Frames 1 - 4 power terminal blocks – Rockwell Automation 1336T FORCE to PowerFlex 700S Phase II Drive Conversion Guide User Manual

Page 21

Advertising
background image

1336 FORCE™ To PowerFlex® 700S Phase II AC Drive Conversion Guide

21

Table C Power Terminal Block (TB1) Specifications

PowerFlex 700S

Frames 1 - 4 Power Terminal Blocks

Drive Frame
Size

Max./Min. Wire Size

(4)

mm2 (AWG)

(4)

Wire sizes given are maximum/minimum sizes that TB1 will accept - these are not recommendations.Use Copper
wire only. Wire gauge requirements and recommendations are based on 75 degree C. Do not reduce wire gauge
when using higher temperature wire.

Maximum Torque
N-m (lb.-in.)

B1

8.4/0.8 (8/18)

1.81 (16)

B2

13.3/0.5 (6/20)

1.70 (15)

C

26.7/0.8 (3/18)

5.65 (50)

D

(1), (2)

(1)

These configurations of TB1 are stud type terminations and require the use of lug type connectors to terminate field
installed conductors. Lug kits are available for use with these configurations. Wire size used is determined by
selecting the proper lug based on the drive catalog number.

(2)

One TE terminal is present – Max./Min. Wire Size is the same as other terminals.

120.0/2.1 (4/0 /14)
67.4/2.1 (00/14)

(5)

(5)

Applies to 30 kW (40 HP) 200-240V, 45 & 56 kW (60 & 75 HP) 380-480V, 56 kW (75 HP) 500-600V drives only.

6.00 (52)
6.00 (52)

E

(1), (3)

(3)

Two TE terminals are present – Max./Min. Wire Size is the same as the D Frame terminal block.

253.0/2.1 (500 MCM/14)

10.00 (87)

F

(1)

303.6/2.1 (600 MCM/14)

23.00 (200)

G

(1)

303.6/2.1 (600 MCM/14)

23.00 (200)

Terminal

Description

Notes

BR1

DC Brake (+)

Dynamic Brake Resistor Connection (+)

BR2

DC Brake (–)

Dynamic Brake Resistor Connection (–)

DC+

DC Bus (+)

DC Input Power or Dynamic Brake Chopper

DC–

DC Bus (–)

DC Input Power or Dynamic Brake Chopper

PE

PE Ground

Not present on 3 Frame drives

Motor Ground

Not present on 3 Frame drives

PS+

Aux +

(1)

(1)

External control power: UL Installation - 300V DC,

±

10%, Non UL Installation - 270-600V DC,

±

10%. Frames 1-3; 40 W, 165

mA, Frame 5; 80 W, 90 mA

PS-

Aux -

(1)

U

U (T1)

To motor

V

V (T2)

To motor

W

W (T3)

To motor

R

R (L1)

AC Line Input Power

S

S (L2)

AC Line Input Power

T

T (L3)

AC Line Input Power

BR1

BR2

DC+

DC–

PE

U (T1)

V (T2)

W (T3)

R (L1)

S (L2)

T (L3)

T

(L3)

S

(L2)

R

(L1)

W

(T3)

V

(T2)

U

(T1)

DC–

DC+

BR2

BR1

Frame 1

Frame 2

Frames 3 & 4

T

(L3)

S

(L2)

R

(L1)

W

(T3)

V

(T2)

U

(T1)

PE

DC–

DC+

BR2

BR1