Powerflex 700s input voltage range/tolerance, X 70, Rang – Rockwell Automation 1336T FORCE to PowerFlex 700S Phase II Drive Conversion Guide User Manual

Page 59: Toler, Ance

Advertising
background image

1336 FORCE™ To PowerFlex® 700S Phase II AC Drive Conversion Guide

59

PowerFlex 700S Input Voltage Range/Tolerance

HP

@ Motor (Drive Output)

Actual Line Voltage (Drive Input)

Full Power Range

Drive Operating Range

Nominal Motor Voltage -10%

Nominal Motor Voltage

Derated Power Range

No Drive

Output

Drive Rated Voltage

Drive Rated Voltage +10%

5 HP

3.7 HP

HP

@ Motor (Drive Output)

Actual Line Voltage (Drive Input)

342V

460V

No Drive

Output

480V

528V

Example:

Calculate the maximum power of a 5 HP, 460V motor
connected to a 480V rated drive supplied with 342V
Actual Line Voltage input.

• Actual Line Voltage / Nominal Motor Voltage = 74.3%

• 74.3%

×

5 HP = 3.7 HP

• 74.3%

×

60 Hz = 44.6 Hz

At 342V Actual Line Voltage, the maximum power the 5
HP, 460V motor can produce is 3.7 HP at 44.6 Hz.

Drive Rating

Nominal Line
Voltage

Nominal Motor
Voltage

Drive Full Power
Range

Drive Operating
Range

200-240

200

200†

200-264

180-264

208

208

208-264

240

230

230-264

380-400

380

380†

380-528

342-528

400

400

400-528

480

460

460-528

500-600
(Frames 1-4 Only)

600

575†

575-660

432-660

500-690
(Frames 5 & 6
Only)

600

575†

575-660

475-759

690

690

690-759

475-759

Drive Full Power Range =

Nominal Motor Voltage to Drive Rated Voltage + 10%.
Rated current is available across the entire Drive Full Power Range

Drive Operating Range
=

Lowest† Nominal Motor Voltage - 10% to Drive Rated Voltage +
10%.
Drive Output is linearly derated when Actual Line Voltage is less
than the Nominal Motor Voltage