1336 FORCE™ To PowerFlex® 700S Phase II AC Drive Conversion Guide

29

PowerFlex 700S - Frame 11

No.

Name

Description

Wire Size Range

(1)

(2)

(1)

Maximum/minimum sizes that the terminal block will accept - these are not recommendations.

(2)

Do Not exceed maximum wire size. Parallel connections may be required.

Torque

Terminal Bolt Size

(3)

(4)

(3)

These connections are bus bar type terminations and require the use of lug type connectors.

(4)

Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal.

Maximum

Minimum

Recommended

1

Input Power Terminal Block

(4)

1L1, 1L2, 1L3, 2L1, 2L2, 2L3

AC Input power

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N-m
(354 lb.-in.)

M12

2

Output Power Terminal Block

(4)

U/T1, V/T2, W/T3

Motor connections

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N-m
(354 lb.-in.)

M12

3

SHLD Terminal, PE, Motor Ground

(4)

Terminating point for wiring shields

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N-m
(354 lb.-in.)

M10

4

DC Bus

(4)

(2 Terminals; DC–, DC+)

DC input

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N-m
(354 lb.-in.)

M12

5

Cable Clamp for Strain Relief

2L1

2L2

2L3

1L1

1L2

1L3

U/T1

V/T2

W/T3

DC-

DC+

3

1

2

4

5