Frame 2 frames 3 & 4 frame 1 – Rockwell Automation 1336T FORCE to PowerFlex 700S Phase II Drive Conversion Guide User Manual

Page 25

Advertising
background image

1336 FORCE™ To PowerFlex® 700S Phase II AC Drive Conversion Guide

25

Power Terminal Block Locations

Frames 1 - 4 Power Terminal Block Locations and Specifications

No. Name

Frame

Description

Wire Size Range

(1)

(1)

Maximum/minimum sizes that the terminal block will accept - these are not recommendations.

Torque

Terminal
Bolt Size

(2)

(2)

Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal.

Maximum

Minimum

Maximum

Recommended

1

Power Terminal Block

1

Input power and motor connections

4.0 mm

2

(10 AWG)

0.5 mm

2

(22 AWG)

1.7 N-m
(15 lb.-in.)

0.8 N-m
(7 lb.-in.)

2

Input power and motor connections

10.0 mm

2

(6 AWG)

0.8 mm

2

(18 AWG)

1.7 N-m
(15 lb.-in.)

1.4 N-m
(12 lb.-in.)

3

Input power and motor connections

25.0 mm

2

(3 AWG)

2.5 mm

2

(14 AWG)

3.6 N-m
(32 lb.-in.)

1.8 N-m
(16 lb.-in.)

BR1, BR2

10.0 mm

2

(6 AWG)

0.8 mm

2

(18 AWG)

1.7 N-m
(15 lb.-in.)

1.4 N-m
(12 lb.-in.)

4

Input power and motor connections

35.0 mm

2

(1/0 AWG)

10 mm

2

(8 AWG)

4.0 N-m
(24 lb.-in.)

4.0 N-m
(24 lb.-in.)

2

SHLD Terminal

1-4

Terminating point for wiring shields

1.6 N-m
(14 lb.-in.)

1.6 N-m
(14 lb.-in.)

3

AUX Terminal Block

1-4

Auxiliary Control Voltage

(3)

PS+, PS-

(3)

External control power: UL Installation - 300V DC, ±10%, Non UL Installation - 270-600V DC, ±10%. Frame 1-6, 100 W

1.5 mm

2

(16 AWG)

0.2 mm

2

(24 AWG)

Frame 2

Frames 3 & 4

Frame 1

BR1

BR2

DC+

DC–

PE

U/T1

V/T2

W/T3

R/L1

S/L2

T/L3

Use 75C Wire Only

#10-#14 AWG

Torque to 7 in-lbs

!

DANGER

BR1 B

SHLD

SHLD

V/T2 W/T3

PE R/L1 S/L2 T/L3

AUX IN+ AUX OUT–

Optional

Communications

Module

75C Cu Wire

6 AWG [10MM

2

] Max.

12 IN. LBS.
1.4 N-M

} TORQUE

WIRE
STRIP

CONTR

OL

PO

WER

BR1 BR2 DC+ DC- U/T1 V/T2 W/T3 R/L1 S/L2 T/L3

Optional

Communications

Module

PE B

PE A

75C Cu Wire

3 AWG [25MM

2

] Max.

16 IN. LBS.
1.8 N-M

} TORQUE

WIRE
STRIP

CONTROL

POWER

AUX IN

+ –

SHLD

SHLD

PE

75C Cu Wire

6 AWG [10MM2] Max.

BR1 BR2

12 IN. LBS.
1.4 N-M

} TORQUE

PE

/

1

3

2

3

1

2

2

1

3

Advertising