English deutsch français english, Deutsch, Français – Rockwell Automation 193-EF Electronic Motor Protection Relay User Manual

Page 4: Italiano, Español italiano español

Advertising
background image

3.4 Main connections
193-EF1A, 193-EF2A
Connection takes place:

Fig. 4

Fig. 5

3.4 Conexiones prin-

cipales 193-EF1A,
193-EF2A
La conexión se hace:

3

.4 Hauptanschlüsse

193-EF1A, 193-EF2A
Der Anschluss erfolgt:

3.4 Raccordements du
193-EF1A, 193-EF2A
Le raccordements se fait:

3.4.1 Without conductor bars
Recommended Motor supply cables

Cable cross-section (flexible strand)

for I

e

=

IEC [mm

2

] CSA, UL [AWG]

20...180 A Fed straight through

4...95

10...0000

10...20 A

Looped through 2x (Fig. 4) 2,5...25 14...10

5...10 A

Looped through 4x (Fig. 5) 1...6

14

2,5...5 A

Looped through 8x

0,75...2,5 14

0,5...2,5 A Looped through 40x

0,5...0,75

English

Deutsch

Français

English

3.4.1 Ohne Stromschienen, mit Durchschlaufen
Empfehlung Motorzuleitungen

Leiterquerschnitt (flexibles Seil)

für I

e

=

IEC [mm

2

] CSA, UL [AWG]

20...180 A direkt durchführen

4...95

10...0000

10...20 A

2x durchschlaufen (Fig. 4) 2,5...25

14...10

5...10 A

4x durchschlaufen (Fig. 5) 1...6

14

2,5...5 A

8x durchschlaufen

0,75...2,5 14

0,5...2,5 A 40x durchschlaufen

0,5...0,75

Deutsch

3.4.1 Sans barres de courant
Recomman- Enroulements primaires Section du fil (fil flexible)
dation pour I

e

=

IEC [mm

2

] CSA, UL [AWG]

20...180 A 1 passage direct

4...95

10...0000

10...20 A

2 passages (Fig. 4)

2,5...25

14...10

5...10 A

4 passages (Fig. 5)

1...6

14

2,5...5 A

8 passages

0,75...2,5 14

0,5...2,5 A 40 passages

0,5...0,75

Français

3.4.1 Senza sbarre, con spire
Raccoman- Linee al motore

Sezione del conduttore (cavo flessibile)

dazione per I

e

=

IEC [mm

2

] CSA, UL [AWG]

20...180 A Far passare direttamente 4...95

10...0000

10...20 A

Formare 2 spire (fig. 4) 2,5...25

14...10

5...10 A

Formare 4 spire (fig. 5) 1...6

14

2,5...5 A

Formare 8 spire

0,75...2,5 14

0,5...2,5 A Formare 40 spire

0,5...0,75

Italiano

3.4.1 Sin barras colectoras, con pasajes
Recomen- Lineas de alimentación Sección transversal del conductor(cable flexible)
dación para I

e

= del motor IEC [mm

2

] CSA, UL [AWG]

20...180 A pasaje directo

4...95

10...0000

10...20 A

2 pasajes (Fig. 4)

2,5...25

14...10

5...10 A

4 pasajes (Fig. 5)

1...6

14

2,5...5 A

8 pasajes

0,75...2,5 14

0,5...2,5 A 40 pasajes

0,5...0,75

Español

Italiano

Español

3.4 Collegamenti principali
193-EF1A ,193-EF2A
Il collegamento ha luogo:

For a convenient

cable

connection to the motor

and contactor up to
2,5 mm

2

, looping

through is carried out
before mounting the
193-EF1A or 193-EF2A,
and the cable ends
being supported by the
2,5 mm

2

connection

terminals 193-HD.

Para

conectar

cómodamente

las líneas

del lado del contactor y

del motor de hasta
2,5 mm

2

, los enrollados

se hacen antes de
montar el 193-EF1A o
bien el 193-EF2A y los
extremos de las líneas
se apoyan sobre los

bornes de conexión de

2,5 mm

2

del 193-HD.

Für bequemes

Ansch-

liessen der schütz- und

motorseitigen Leitungen
bis 2,5 mm

2

werden die

Schlaufungen vor der
Montage des 193-EF1A
bzw. 193-EF2A ausgef-
ührt und die Leitungs-
enden auf den

Anschluss-

klemmen 2,5 mm

2

193-HD abgestützt.

Pour faciliter

le raccor-

dement des fils côtés

contacteur et moteur
dans le cas d’une section
de fil ne dépassant pas
2,5 mm

2

, les enroule-

ments seront pratiqués
avant le montage du
193-EF1A ou du
193-EF2A. Les raccor-
dements se feront
ensuite à l’aide des

bornes de 2,5 mm

2

193-HD.

Per rendere più facili i

collegamenti dei cavi lato

contattore e motore fino a
2,5 mm

2

, le spire vengono

eseguite prima del
montaggio del 193-EF1A,
rispettivamente 193-EF2A.
I collegamenti verranno
quindi eseguiti mediante i

morsetti da 2,5 mm

2

193-HD.

4

193-EF

4

193-EF

2