Wiring, Terminal designations for conduit entrance – Rockwell Automation 284D ArmorStart - Getting Started User Manual

Page 11

Advertising
background image

Publication 284D-QS001D-EN-P - July 2006

11

Wiring

Power, Control, Safety Monitor Inputs, and Ground Wiring

Table 1 provides the power, control, safety monitor inputs, ground wire
capacity and the tightening torque requirements. The power, control,
ground, and safety monitor terminals will accept a maximum of two wires
per terminal.

Table 1

Power, Control, Safety Monitor Inputs, Ground Wire Size, and Torque

Specifications

Terminal Designations for
Conduit Entrance

As shown in Figure 9, the ArmorStart Distributed Motor Controller contains
terminals for power, control, safety monitor inputs, and ground wiring.
Access can be gained by removing the terminal access cover plate.

Figure 9 ArmorStart Power, Control, and Safety Monitor Terminals

Terminals

Wire Size

Torque

Wire Strip Length

Power

and

Ground

Primary/Secondary

Terminal:

1.0…4.0 mm

2

(#18 …#10 AWG)

Primary Terminal:

10.6…21.6 lb.-in.

(1.2…2.4 N•m)

Secondary Terminal:

5.3…7.3 lb.-in

(0.6…0.8 N•m)

0.35 in. (9 mm)

Control and Safety

Monitor Inputs

0.34mm

2

…4.0 mm

2

(#22…#10 AWG)

5.0…5.6 lb.-in

(0.6 N•m)

0.35 in. (9 mm)

Primaries

Secondaries

Advertising