Default Input and Output (I/O) Assembly Formats

The I/O assembly formats for the ArmorStart

are identified by the value in

Parameter 11 (Consumed IO Assy.) and Parameter 12 (Produced IO Assy.).
These values determine the amount and arrangement of the information
communicated to the master scanner. The tables below identify the default
information produced and consumed by Bulletin 284 devices. For additional
formats and advance configurations please reference the user manual:

Defaults for Bulletin 284 Distributed Motor Controllers

Table 4

Instance 164 — Default Consumed Inverter Type Distributed Starter

(4 bytes)

Table 5

Instance 165 — Default Produced Inverter Type Distributed Starter

(4 bytes)

➊ Refers to output contactor status.
➋ Refers to source brake contactor status.

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

User

Out B

User

Out A

Jog
Rev

Jog Fwd

Fault Reset

Run Rev

Run Fwd

1

Drive

In 4

Drive

In 3

Drive

In 2

Drive

In 1

Decel Rate 2

Enable

Decel Rate 1

Enable

Accel Rate 2

Enable

Accel Rate 1

Enable

2

Comm Frequency Command (Low) (xxx.x Hz)

3

Comm Frequency Command (High) (xxx.x Hz)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

At

Reference

Net Ref

Status

Net Ctl

Status

Ready

Running

Rev

Running

Fwd

Alarm

Tripped

1

Contactor 2

Contactor 1

140M

On

HOA

Status

Input 3

Input 2

Input 1

Input 0

2

Output Frequency (Low) (xxx.x Hz)

3

Output Frequency (High) (xxx.x Hz)