Lsdlsd msdmsd – Rockwell Automation 284D ArmorStart - Getting Started User Manual
Page 22
 
22
Publication 284D-QS001D-EN-P - July 2006
To set an address using the hardware rotary switches, simply set the 
switches to the desired node address. To access the node address rotary 
switches, three-phase and control power should be turned off. Then remove 
the starter module from the base unit. The rotary node address switches are 
located on the back side of the starter module. Change the switches to the 
desired node address. Re-install the starter module to the base unit. Reapply 
power and the device will re-start at the new address.
Figure 15 Rotary Node Address Configuration
System Configuration Information
The following information is provided to identify the default method for 
setting up communication to the ArmorStart. Additional configuration 
information and advanced settings help can be found in the ArmorStart User 
Manual, Publication 284-UM001*-EN-P. 
Using Automap Feature with Default Input and Output (I/O) Assemblies
The Automap feature available in all Rockwell Automation scanners will 
automatically map the information as shown below. If manual mapping is 
required, the information below can be used to map a device based on the 
default configuration.
Table 3
Default I/O Messaging Data
LSDLSD
MSDMSD
Default
Message type
Polled
Consumed data size
4 byte (Rx)
Produced data size
4 bytes (Tx)