Rockwell Automation 284D ArmorStart - Getting Started User Manual
Page 18
 
18
Publication 284D-QS001D-EN-P - July 2006
The working space around the ArmorStart may be minimized as the 
ArmorStart does not require examination, adjustment, servicing or 
maintenance while energized. In lieu of this service, the ArmorStart is 
meant to be unplugged and replaced after proper lockout/tag-out procedures 
have been employed.
Since the ArmorStart is available with a factory installed HOA keypad 
option this may require the ArmorStart to be selected and installed as 
follows if the application requires frequent use of the hand operated 
interface by the equipment operator: 
1. They are not less than 0.6 m (2 ft) above the servicing level and are
within easy reach of the normal working position of the operator.
2. The operator is not placed in a hazardous situation when operating
them.
3. The possibility of inadvertent operation is minimized.
If the operated interface is used in industrial establishments where the 
conditions of maintenance and supervision ensure that only qualified 
persons operate and service the ArmorStart's operator interface, and the 
installation is located so that inadvertent operation is minimized then other 
installation locations with acceptable access can be provided. 
DeviceNet Network Installation
The ArmorStart Distributed Motor Controller contains the equivalent of 
30 in. (0.76 m) of Device Net drop cable's electrical characteristics and 
therefore 30 in. of drop cable must be included in the DeviceNet drop cable 
budget for each ArmorStart in addition to actual drop cable required for the 
installation.
Other DeviceNet System Design Considerations
The separation of the control power and DeviceNet power is recommended 
as a good design practice. This minimizes the load on the DeviceNet supply, 
and prevents transients which may be present on the control power system 
from influencing the communication controls.