Rockwell Automation 198x Modular DeviceNet Starter Auxiliary I/O User Manual
Page 100

5-34 Specifications
Publication 198-UM001B-EN-P September 2001
Figure 5.23 198-OW2S-Q5 Electrical and Application Schematic
Table 5.X 198-OW2S-Q5 Specifications
Connector (M12 Female 3-Pin)
M12 Mounting Hole
16 mm (5/8 in.) M12
M12 Thread
M12 x 1 mm
M12 Connector Torque
1.4 Nm (12 lb-in.)
Electrical
Module Operating Voltage Range
11…25V DC
Module Voltage Rating
24V DC
Module Current Draw
40 mA @ 24V DC
Output Voltage Rating
24V DC
Output Load Current
0.5 A total (Out A + Out B)
Switching Device
Relay — B300, AC15, DC13
Module Isolation
132V AC working voltage
1500V AC for 1 s
Environmental
Ambient Temperature
Operating
–25…+60
°C (–4…+140°F)
Storage
–40…+85
°C (–40…+185°F)
Relative Humidity
0…95% non-condensing
Shock
Operating
30 g peak acceleration
Non-Operating
50 g peak acceleration
Operating Vibration
10 g @ 58…2000 Hz
0.060 in. peak-to-peak displacement 2…57 Hz
Per IEC 68-2-6
Approvals
Agency Certification
(when product is marked)
cUL
UL Listed
CE marked for all applicable directives
1
2
3
4
5
Not
Used
0V
24V DC
PE
PE
PE
PE
Ou t B
Ou t A
Typical Installation and Wiring