Input assembly instance105 – Rockwell Automation 198x Modular DeviceNet Starter Auxiliary I/O User Manual
Page 153

DeviceNet Information A-13
Publication 198-UM001B-EN-P September 2001
Input Assembly Instance 105
This assembly reserves a byte (8 bits) for every module on the system — regardless of
whether it has any inputs. The assembly size is eight bytes — two for status and six for data.
This is the default assembly for 198-DNG module. The following is a generalization of the
input assembly instance. The status and error codes follow on pages A-15 and A-16.
Table A.18 Input Assembly Instance 105
Slot
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
—
0
Module
Error
Number 1
Module
Error
Number 0
I/O
Module
Status 6
I/O
Module
Status 5
I/O
Module
Status 4
I/O
Module
Status 3
I/O
Module
Status 2
I/O
Module
Status 1
—
1
Error
Code 6
Error
Code 5
Error
Code 4
Error
Code 3
Error
Code 2
Error
Code 1
Error
Code 0
Module
Error
Number 2
1
2
—
—
—
—
—
—
Input 2
Input 1
2
3
—
—
—
—
—
—
Input 2
Input 1
3
4
—
—
—
—
Open
Short
Input 2
Input 1
4
5
—
—
—
—
—
—
—
—
5
6
—
—
—
—
—
—
Input 2
Input 1
6
7
—
—
—
—
—
—
Input 2
Input 1