Discrete input point object— class id (08hex), Discrete output point object — class id (09hex), Discrete input point object — class id (08hex) – Rockwell Automation 198x Modular DeviceNet Starter Auxiliary I/O User Manual
Page 157

DeviceNet Information A-17
Publication 198-UM001B-EN-P September 2001
Discrete Input Point Object — Class ID (08hex)
Multiple instances of the Discrete Input Object are supported. All instances contain the
following attributes:
Discrete Output Point Object — Class ID (09hex)
Table A.22 Discrete Input Object Class Attributes
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Revision
UINT
2
2
Get
Max Instances
UINT
0…64
Table A.23 Discrete Input Object Instance Attributes
Attribute ID
Access Rule
Name
Data Type
Value
3
Get
Value
BOOL
Input point Value.
0 = OFF
1 = ON
5
Get/Set
Off_On Delay
UINT
0
µs
2000
µs
4000
µs
8000
µs
16000
µs
6
Get/Set
On_Off Delay
UINT
0
µs
2000
µs
4000
µs
8000
µs
16000
µs
Table A.24 Discrete Input Object Common Services
Service Code
Implemented for:
Service Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
Table A.25 Discrete Output Object Class Attributes
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Revision
UINT
1
2
Get
Max Instances
UINT
0…80