Presence sensing object — class id (0ehex) – Rockwell Automation 198x Modular DeviceNet Starter Auxiliary I/O User Manual
Page 158

A-18 DeviceNet Information
Publication 198-UM001B-EN-P September 2001
Multiple instances of the Discrete Output Object will be supported. All instances will contain
the following attributes:
Presence Sensing Object — Class ID (0Ehex)
Table A.26 Discrete Output Object Instance Attributes
Attribute ID
Access Rule
Name
Data Type
Value
3
Get/Set
Value
BOOL
0 = OFF
1 = ON
5
Get/Set
Fault Action
BOOL
0 = Go to Fault value
1 = Hold Last State
6
Get/Set
Fault Value
BOOL
0 = OFF
1 = ON
7
Get/Set
Idle Action
BOOL
0 = Go to Idle value
1 = Hold Last State
8
Get/Set
Idle Value
BOOL
0 = OFF
1 = ON
Table A.27 Discrete Output Object Common Services
Service Code
Implemented for:
Service Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
Table A.28 Presence Sensing Object Class Attributes
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Revision
UINT
1
2
Get
Max Instances
UINT
0…32