Input assembly instance107 – Rockwell Automation 198x Modular DeviceNet Starter Auxiliary I/O User Manual
Page 154

A-14 DeviceNet Information
Publication 198-UM001B-EN-P September 2001
Input Assembly Instance 107
This assembly reserves a byte (8 bits) for every module on the system — regardless of
whether it has any inputs. The size of the assembly 20 bytes — four for status and 16 for data.
This is the default assembly for 198-DN module. The following is a generalization of the
input assembly instance. The status and error codes follow on pages A-15 and A-16.
Table A.19 Input Assembly Instance 107
Slot
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Module
Status 8
Module
Status 7
Module
Status 6
Module
Status 5
Module
Status 4
Module
Status 3
Module
Status 2
Module
Status 1
1
Module
Status
16
Module
Status
15
Module
Status
14
Module
Status
13
Module
Status
12
Module
Status
11
Module
Status
10
Module
Status 9
2
Module Error Number
3
Error Code
1
4
—
—
—
—
—
—
Input 2
Input 1
2
5
—
—
—
—
—
—
Input 2
Input 1
3
6
—
—
—
—
Open
Short
Input 2
Input 1
4
7
—
—
—
—
—
—
—
—
5
8
—
—
—
—
—
—
Input 2
Input 1
6
9
—
—
—
—
—
—
Input 2
Input 1
7
10
—
—
—
—
—
—
—
—
8
11
—
—
—
—
—
—
—
—
9
12
—
—
—
—
—
—
—
—
10
13
—
—
—
—
—
—
—
—
11
14
—
—
—
—
—
—
—
—
12
15
—
—
—
—
—
—
—
—
13
16
—
—
—
—
—
—
—
—
14
17
—
—
—
—
—
—
—
—
15
18
—
—
—
—
—
—
—
—
16
19
—
—
—
—
—
—
—
—