GuardShield™ Type 2 Safety Light Curtain Installation Instructions

12

R

Original instructions

Troubleshooting Guide

The light curtain carries out an internal self-test after startup. If an error
occurs, an appropriate signal combination is sent through the LEDs to
the transmitter and receiver.

Condition

No.

Error Description

Action

6

Internal fault, receiver

• Replace receiver

7

Internal fault, transmitter

• Check connections transmitter/

receiver

• Exchange transmitter

8

External fault

• Check connections of OSSD

outputs for short circuit against
+24V DC and GND (cable,
connected devices)

• Replace receiver

9

External fault (MPCE error)
The function Relay monitoring is
activated and after clearing the OSSD
the input Relay monitoring does not
recognize a change of state.

• Check connection Relay

monitoring

• Check connected relay for closed

contact (if OSSD ON—input Relay
monitoring must have GND level,
if OSSD OFF—input Relay
monitoring must have +24V)

• Switch on only after POWER OFF/

ON