GuardShield™ Type 2 Safety Light Curtain Installation Instructions

13

R

Original instructions

System Status Indicators

6 through 9 = Fault conditions

Flash rate is approximately. 2 Hz (2 times per second)

Note: For fault conditions 6 through 9, see Troubleshooting guide on page 12.

Receiver LEDs

Transmitter LEDs

Condition No.

OSSDs

OFF

Red

OSSDs

ON

Green

Alignment

Amber

Interlock

Yellow

Power

On

Amber

Emitting

Yellow

1

OFF

ON

OFF

OFF

ON

ON

2

ON

OFF

OFF

OFF

ON

ON

3

ON

OFF

ON

OFF

ON

ON

4

ON

OFF

OFF

ON

ON

ON

5

ON

OFF

OFF

OFF

ON

OFF

6

FLASH

OFF

OFF

OFF

ON

ON

7

ON

OFF

OFF

OFF

FLASH

ON

8

FLASH

OFF

ON

OFF

ON

ON

9

FLASH

OFF

OFF

ON

ON

ON

Condition No.

Description

1

Guard only mode, light curtain unobstructed (aligned, not in interlock)

2

Guard only mode, light curtain interrupted (aligned, not in interlock)

3

Guard only mode, misaligned (not in interlock)

4

Restart interlock (aligned)

5

Transmitter test input active (pin 4)

6

Internal fault, receiver

7

Internal fault, transmitter

8

External fault (OSSD short to ground, +V, or cross connection)

9

External fault (MPCE/EDM error)

Receiver

Transmitter

OSSDs

OFF

Power Emitting

OSSDs

ON

Alignment Interlock