1pt 1ct line-to-neutral, 1pt 1ct line-to-line – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 18

Advertising
background image

18 PowerMonitor 1000 Unit

Rockwell Automation Publication 1408-IN001E-EN-P - September 2013

1PT 1CT Line-to-line

1PT 1CT Line-to-neutral

This special wiring mode is designed for use in new capacitor bank controller installations where

the legacy metering connections described in the preceding section do not apply. In this mode,

the power monitor returns values as if it were configured in Wye mode. Three-phase values are

estimated assuming a balanced load.
The following wiring diagram indicates the connections for the 1PT 1CT Line-to-neutral mode.

A PT is optional. Wiring diagnostics are disabled in this mode.

V1

L1

L2

L3

V2

VN

V3

Load

Line

Ground

Voltage Mode = 1PT1CT Line-to-line

PowerMonitor 1000

Fuses

(by user)

PT

(by user)

CT

(by user)

Shorting terminal

block (by user)

I1+

I2+

I1-

I2-

Ground