Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 41

Advertising
background image

PowerMonitor 1000 Unit 41

Rockwell Automation Publication 1408-IN001E-EN-P - September 2013

Waiting Command - five minutes have elapsed since the most recent command.

Out of Range - measured phase angles are outside the range of the selected system power
factor.

Voltage or current input missing (input below the metering threshold) or inverted
(reverse polarity, 180 degrees out of phase)

-1 — Test not run; see wiring status for reason.

0 — Pass, all inputs present / correct polarity.

1 — Phase 1 missing / inverted.

2 — Phase 2 missing / inverted.

3 — Phase 3 missing / inverted.

12 — Phase 1 and 2 missing / inverted.

13 — Phase 1 and 3 missing / inverted.

23 — Phase 2 and 3 missing / inverted.

123 — All 3 phases missing / inverted.

Voltage rotation

-1 — Test not run; see wiring status for reason.

123 — Forward phase rotation (ABC).

132 — Reverse phase rotation (ACB).

4 — Invalid phase rotation (2 inputs wired with same phase).

Current rotation, referenced to voltage Phase 1

-1 — Test not run; see wiring status for reason.

123 — Forward rotation (ABC).

231 — Forward rotation, 120 degrees displaced (BCA).

312 — Forward rotation, 240 degrees displaced (CAB).

132 — Reverse rotation (ACB).

213 — Reverse rotation, 120 degrees displaced (BAC).

321 — Reverse rotation, 240 degrees displaced (CBA).

4 — Invalid phase rotation (2 inputs wired with same phase).

Forward phase rotation is not required to pass wiring diagnostics. Before changing wiring

connections, refer to both the voltage / current rotation and voltage / current inverted status to

select the correct analog input.