Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 72

72 PowerMonitor 1000 Unit
Rockwell Automation Publication 1408-IN001E-EN-P - September 2013
Parameter
Rating
Control Power
85…264V AC 47…63 Hz
125…250V DC
4 VA max
Voltage Sense Inputs: V1, V2, V3
Input impedance: 5 M min
Input current: 2 mA max
Current Sense Inputs: I1, I2, I3
Overload withstand:
15 A continuous, 200 A for 1/2 s
Burden: 0.05V A
Impedance: 0.002
Max crest factor at 5 A is 3.0
Starting current: 5 mA
Status Inputs
Contact closure (internal 24V DC)
KYZ Output
80 mA at 240V AC / 300V DC
Attribute
Value
Dielectric withstand
Control power
2500V
Voltage inputs
2500V
Current inputs
2500V
Status inputs
2500V
KYZ output
2500V
Terminal blocks
0.34…2.5 mm
2
(22…14 AWG), 75 °C (167 °F) min, copper wire only
Recommended torque 0.8 N•m (7 lb•in)
Operating
temperature
-10…60 °C (14…140 °F)
Storage temperature
-40…85 °C (-40…185 °F)