Metered Parameters

The power monitor calculates and returns the following demand values:

Real power demand, kW

Reactive power demand, kVAR

Apparent power demand, kVA

Demand power factor, percent lagging (-) or leading (+)

Projected kW, kVAR, and kVA demand

Demand interval elapsed time, minutes

Projected demand calculates a linear projection of demand at the end of a demand interval.
Demand power factor is calculated using the following formula.

kW Demand / kVA Demand

Setup

Demand metering requires basic analog input setup as well as demand calculation setup. Basic

demand set-up parameters are found in the Advanced Setup menu. Network demand

synchronization is available on units connected to an Ethernet network. Network-demand

synchronization set-up parameters are found in the Ethernet communication set-up menu.