Glossary – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 74

Advertising
background image

74 PowerMonitor 1000 Unit

Rockwell Automation Publication 1408-IN001E-EN-P - September 2013

Glossary

ampere. A unit of electrical current or rate of flow of electrons. One volt across one ohm of

resistance causes a current flow of one ampere.
apparent power. The product of voltage magnitude and current magnitude in a circuit. Units

are VA or some multiple thereof.
balanced load. An alternating, current power system consisting of more than two current

carrying conductors in which these current-carrying conductors all carry the same current.
baud. A rate at which data transmission occurs, where one baud equals one bit per second.
billing demand. The demand level that a utility uses to calculate the demand charges on the

current month’s bill. Various methods may be used to determine the value, such as minimum

demand, peak demand, or a ratchet clause. It can be based on Watt demand, VA demand, VAR

demand, or some combination of these.
burden. The electrical load placed on source of VA or the load an instrument or meter places on

a current or potential transformer. All current and potential transformers have a rated burden

that should not be exceeded or else transformer transformation accuracy deteriorates.
capacitor. A device consisting essentially of two conducting surfaces separated by an insulating

material or dielectric. A capacitor stores electrical energy, blocks the flow of direct current, and

permits the flow of alternating current to a degree dependent upon the capacitance and

frequency. They may also be used to adjust the power factor in a system.
connected load. The total load that you can impose on the electrical system if everything was

connected at one time. Connected loads can be measured in horsepower, watts or volt-amperes.

Some rate schedules establish a minimum demand charge by imposing a fee per unit of

connected load.
current transformer (CT). A transformer, intended for measuring or control purposes, designed

to have its primary winding connected in series with a conductor carrying the current to be

measured or controlled. CT’s step down high currents to lower values that can be used by

measuring instruments.
current transformer ratio. The ratio of primary amperes divided by secondary amperes.
data table. The power monitor data is organized in data tables similar to those found in an

SLC 5/03 programmable controller. The detailed data-table definitions are covered in the

PowerMonitor 1000 Communication Reference Manual, publication

1408-UM001

.

demand interval. Demand charges are based on peak demand over a utility-specified time

interval, not on the instantaneous demand (or connected load) at any given moment. Typical

demand intervals are 15, 20, and 30 minutes.
frequency. The number of recurrences of a periodic phenomenon in a unit of time. In electrical

terms, frequency is specified as so many Hertz (Hz) where one Hz equals one cycle per second.
impedance. The total opposition (that is, resistance and reactance) a circuit offers to the flow of

alternating current at a given frequency. It is measured in ohms.
inductor. A device consisting of one or more windings with or without a magnetic core. Motors

are largely inductive.

Advertising
This manual is related to the following products: