Connect the DeviceNet Cable

Follow these procedures to connect the DeviceNet cable to the base
block. We do not supply the DeviceNet connector with the base
block. You must purchase the connector separately. These are the
types of connectors you order directly from Rockwell Automation.

• 1799-DNETCON - 5-position open-style connector
• 1799-DNETSCON - 5-position open-style connector with

locking screws

• 1799-DNC5MMS - 5-position open-style to 12 mm connector

with locking screws

1 . Connect the DeviceNet wiring (drop line) to one of the

DeviceNet connectors as shown in the figure, noting that a
color-coded wiring diagram is printed next to the connector
on the left side of the base block.

WARNING

If you connect or disconnect the DeviceNet cable with power applied
to this module or any device on the network, an electrical arc can
occur. This could cause an explosion in hazardous location
installations.

Be sure that power is removed or the area is nonhazardous before
proceeding.

Wiring Diagram for
1799-DNETCON

Wiring Diagram for
1799-DNC5MMS Connector

Drain/Shield

Can_H White

Can_L Blue

V+ Red

V- Black

V- Black

Can_L Blue

Drain/Shield

Can_H White

V+ Red

Connector

44186