Cable break procedures – Rockwell Automation 1790D-XXXX DeviceNet Digital Base Terminal Block CompactBlock LDX I/O Series A User Manual
Page 17

DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 17
Publication
1790-IN006C-EN-P - May 2006
Cable Break Procedures
A cable break in any location between either of the following
produces data of 1 in the data table for all inputs down stream of the
cable break.
• Base and digital input expansion module
• Digital input expansion module and another digital input
expansion module
Solid Green
The module is operating in a normal
condition, and the module is online with
connections in the established state. As
a group 2 module, the module is
allocated to a master.
None.
Flashing
Green
The module is online with no
connections in the established state.
Establish connections to other
nodes. As a group 2 module,
allocate the module to a
master.
Off
No power.
Wait until the module has
completed the dup_MAC_id
test or power the module.
Function
LED Color
Module Illumination
Condition
I/O Status
Outputs
Each output:
Green
None
Green
Output is not energized.
Output is energized.
Inputs
Each input:
Green
None
Green
No valid input is present.
Valid input is present.
Indication
Probable Cause
Recommended Action