Cable break procedures – Rockwell Automation 1790D-XXXX DeviceNet Digital Base Terminal Block CompactBlock LDX I/O Series A User Manual

Page 17

Advertising
background image

DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 17

Publication

1790-IN006C-EN-P - May 2006

Cable Break Procedures

A cable break in any location between either of the following
produces data of 1 in the data table for all inputs down stream of the
cable break.

• Base and digital input expansion module
• Digital input expansion module and another digital input

expansion module

Solid Green

The module is operating in a normal
condition, and the module is online with
connections in the established state. As
a group 2 module, the module is
allocated to a master.

None.

Flashing
Green

The module is online with no
connections in the established state.

Establish connections to other
nodes. As a group 2 module,
allocate the module to a
master.

Off

No power.

Wait until the module has
completed the dup_MAC_id
test or power the module.

Function

LED Color

Module Illumination

Condition

I/O Status

Outputs

Each output:
Green

None
Green

Output is not energized.
Output is energized.

Inputs

Each input:
Green

None
Green

No valid input is present.
Valid input is present.

Indication

Probable Cause

Recommended Action