16 DeviceNet Digital Base Terminal Block CompactBlock LDX I/O

Publication

1790-IN006C-EN-P - May 2006

2. Attach the connector to the base block once you have

properly wired the drop line to the connector.

3. Use the locking screws on the connector to fasten it to the

base block, if applicable.

Interpret the LED Indicators

Read this section for information about how to interpret base block
LED indicators. The base block has the following indicators.

• Block status
• Network status
• I/O status

If a module status indicator is flashing red, refer to the cable break
procedures section.

Indication

Probable Cause

Recommended Action

Module Status

Solid Red

Unrecoverable fault in base unit.

Replace base block.

Flashing Red

Fault in expansion unit.

Reconnect or replace, as
needed.

Solid Green

Normal operation.

None.

Off

No power.

Apply power to device.

Network Status

Solid Red

Module node number is a duplicate of an
existing node, or network
communication issues exist.

Change module node number
to an unused address, or verify
network wiring is correct and
communication is stable.

Flashing Red

An I/O connection has timed out.

Cycle power to the module.