All digital-expansion inputs produce data of 1 if the expansion cable 
is removed. No status is in the produced assembly. Attribute 101 in 
the identity object reports module faults. If no faults are present, an 
explicit message GET command returns 0. If the ribbon cable is 
disconnected, it returns 0x04, which is for module location change. 
The module LED also flashes indicating a fault if an expansion is 
disconnected.
To determine if the data is valid, continuously send an explicit 
message to the module to check the status of the input conditions 
since no status word is in the I/O mapping data table. 
• Class = 1
• Instance = 1
• Attribute = 101 (0x65)
To detect the loss of communication to the expansion module, use 
one of these methods. 
• If an unused input is available, tie the unused input on the last
expansion low. If that input goes high with a value of 1, a loss 
of communication to the expansion or expansions occurred.
• If no unused input is available, check expansion inputs for the
condition of all on. To check validity in this case, send an 
explicit message to the identity object class 1, instance 1, 
attribute 101 (0x65). A returned value of 0 indicates the input 
data is good.