24 DeviceNet Digital Base Terminal Block CompactBlock LDX I/O

Publication

1790-IN006C-EN-P - May 2006

EFT/B Immunity

IEC 61000-4-4
±1 kV at 5 kHz on power ports
±2 kV at 5 kHz on signal ports
±2 kV at 5 kHz on communications ports

Surge Transient Immunity

IEC 61000-4-5:
±1 kV line-line (DM) on power ports
±1 kV line-line (DM) on signal ports
±2 kV line-earth (CM) on communications ports

Conducted RF Immunity

IEC61000-4-6
10V rms with 1 kHz sine-wave 80%AM at 150 kHz...80 MHz

Enclosure Type Rating

None (open-style)

Mounting

DIN rail or panel

Dimension

52 x 104 x 42 mm (2.03 x 4.07 x 1.64 in.)

Weight

0.1 kg (0.3 lb)

Wiring, Terminal Block
(M3.0) Screw Torque

7 lb-in max (use copper or copper-clad aluminum
conductors)

Wire Size

2.5…0.25 mm

2

(14 …22 AWG) solid or stranded copper

wire rated at 75 °C or greater 1.2 mm (3/64 in.) insulation
max

Wiring Category

(1)

2 - on signal ports
2 - on power ports
2 - on communications ports

dc Field Power

Supply voltage - 24V dc nom
Voltage range - 10…28.8V dc

dc Relay Coil Power

Supply voltage - 24V dc nom
Voltage range - 19.2…28.8V dc

ac Field Power

Supply voltage - 115V ac, 60 Hz
Voltage range - 85…132V ac, 47…63 Hz

DeviceNet

DeviceNet Power

Supply voltage - 24V dc nom
Voltage range - 8…28V dc

Environmental - Common To All Base Blocks in This Publication