14 SLC ControlNet Scanner Module

Publication 1747-IN059C-EN-P - September 2001

OK Indicator and Display Mnemonics

The OK indicator is handled consistently with the ControlNet
specifications for the Identity object.

Sequence OK

Indicator

Alpanumeric
Display

Module Status
Word (M1 file)

Description

Probable
Cause

Recommended
Action

Startup

Alternately
red/ green

POST

N/A

The
1747-SCNR
module is
running Power
On Self Test.

Power was
applied to the
module.

No action
required.

FIRM
WARE

N/A

1747-SCNR
firmware
revision. This is
a temporary
display after
startup.

Power was
applied to the
module.

No action
required.

Run time

Green

A#XX

N/A

ControlNet
node address

None

No action
required.

I/O

0x26

All configured
connections
are
established.

None

No action
required.

IDLE

N/A

The scanner is
in idle mode.

The SLC
processor or
adapter in
slot 0 is in
program
mode or the
Scanner
Mode
Command bit
of the Module
Command
word is clear
(O:x.0/10
where x is the
scanner slot
number).

If you want to
put the scanner
into run mode,
put the SLC
processor in
slot 0 into run
mode and set
the Scanner
Mode
Command bit of
the Module
Command word
(O:x.0/10) using
an
unconditional
OTE instruction.

RUN

N/A

The scanner is
in run mode.

The SLC
processor in
slot 0 is in run
mode and the
Scanner
mode
Command bit
of the Module
Command
word is set
(O:x.0/10).

If you want to
put the scanner
into program
mode, either
put the SLC
processor in
slot 0 into
program mode
or clear the
Scanner Mode
Command bit of
the Module
Command word
(O:x.0/10).