Rockwell Automation 1747-SCNR SLC ControlNet Scanner Module Installation Instructions User Manual
Page 18
 
18 SLC ControlNet Scanner Module
Publication 1747-IN059C-EN-P - September 2001
Sequence OK
Indicator
Alpanumeric 
Display
Module Status 
Word (M1 file)
Description
Probable 
Cause
Recommended 
Action
Errors
Off
None
N/A
Module is not 
communicating
Power supply 
fault.
Check power 
supply, cable 
connectors, and 
seat module 
firmly in 
chassis.
Flashing 
Green
N/A
0x43
Network error
Cable error or 
no other 
nodes on the 
network.
Verify network 
cabling.
Red
(Scrolling 
display 
showing fault 
details)
N/A
Module faulted
Internal error 
detected.
Record fault 
details and 
contact 
Rockwell 
Automation 
representative 
or distributor.
Flashing 
Red
A#00
FLSH
CFG
ERAS
0x42
Module erased 
network and 
connection 
configuration 
stored in flash
Network node 
address set 
to 00.
Power down 
the module and 
change the 
address 
switches.
DUPL
A#XX
0x44
Duplicate node 
address
Another 
device with 
the same 
ControlNet 
address is on 
the link.
Power down 
the 1747-SCNR 
module and 
change the 
network 
address 
switches to a 
correct node.