18 SLC ControlNet Scanner Module

Publication 1747-IN059C-EN-P - September 2001

Sequence OK

Indicator

Alpanumeric
Display

Module Status
Word (M1 file)

Description

Probable
Cause

Recommended
Action

Errors

Off

None

N/A

Module is not
communicating

Power supply
fault.

Check power
supply, cable
connectors, and
seat module
firmly in
chassis.

Flashing
Green

N/A

0x43

Network error

Cable error or
no other
nodes on the
network.

Verify network
cabling.

Red

(Scrolling
display
showing fault
details)

N/A

Module faulted

Internal error
detected.

Record fault
details and
contact
Rockwell
Automation
representative
or distributor.

Flashing
Red

A#00
FLSH
CFG
ERAS

0x42

Module erased
network and
connection
configuration
stored in flash

Network node
address set
to 00.

Power down
the module and
change the
address
switches.

DUPL
A#XX

0x44

Duplicate node
address

Another
device with
the same
ControlNet
address is on
the link.

Power down
the 1747-SCNR
module and
change the
network
address
switches to a
correct node.