Rockwell Automation 1747-SCNR SLC ControlNet Scanner Module Installation Instructions User Manual

Page 17

Advertising
background image

SLC ControlNet Scanner Module 17

Publication 1747-IN059C-EN-P - September 2001

Sequence OK

Indicator

Alpanumeric
Display

Module Status
Word (M1 file)

Description

Probable
Cause

Recommended
Action

Run time

Flashing
Green

EDIT

N/A

The scanlist in
the 1747-SCNR
is being
modified.

Edits have
been enabled
with
RSNetWorx
for
ControlNet.

Note:
Previously
configured
connections
will be
reestablished
if lost. Newly
configured or
changed
connections
will not be
established
until edits are
accepted.

Finish
modifying the
scanlist with
RSNetWorx for
ControlNet and
then accept
edits.

Cancel edits
with
RSNetWorx for
ControlNet.

SIGM

N/A

A scanner
signature
mismatch has
been detected.
The
1747-SCNR
scanner
signature does
not match the
signature
stored in the
active keeper.

The scanner is
not able to start
any scheduled
communication
to remote
devices. Only
unscheduled
communication
is possible.

Module is not
configured
properly.

Use RSNetWorx
for ControlNet
to schedule the
existing
configuration.

Use RSNetWorx
for ControlNet
to download a
new
configuration.