Rockwell Automation 1747-SCNR SLC ControlNet Scanner Module Installation Instructions User Manual
Page 16
 
16 SLC ControlNet Scanner Module
Publication 1747-IN059C-EN-P - September 2001
Sequence OK
Indicator
Alpanumeric 
Display
Module Status 
Word (M1 file)
Description
Probable 
Cause
Recommended 
Action
Run time
Flashing 
Green
I/O
I/O
I/O
I/O
0x22
0x23
0x24
0x25
Connections 
are configured 
but no 
connections 
are 
established.
Connections 
are configured 
but only 
25% are 
successfully 
established.
50%
75%
View the 
Connection 
Status screen 
in RSNetWorx 
for ControlNet 
to see why 
the 
connections 
are not 
established.
Check to see if 
the 1747-SCNR 
and the remote 
devices are 
correctly 
connected to 
the ControlNet 
network.
Module 
bandwidth is 
exceeded.
Reduce the 
number of 
scheduled 
connections by:
- using a 
discrete rack 
connection 
instead of 
multiple 
discrete module 
connections
- combining 
multiple I/O 
racks into a 
single I/O rack
- combining 
multiple 
peer-to-peer 
messages into 
one message.
Increase your 
Network Update 
Time and/or 
increase the 
Requested 
Packet Intervals 
for scheduled 
data transfers.
Increase your 
SLC 500 ladder 
program scan 
by adding more 
logic.