16 SLC ControlNet Scanner Module

Publication 1747-IN059C-EN-P - September 2001

Sequence OK

Indicator

Alpanumeric
Display

Module Status
Word (M1 file)

Description

Probable
Cause

Recommended
Action

Run time

Flashing
Green

I/O

I/O

I/O

I/O

0x22

0x23

0x24

0x25

Connections
are configured
but no
connections
are
established.

Connections
are configured
but only
25% are
successfully
established.

50%

75%

View the
Connection
Status screen
in RSNetWorx
for ControlNet
to see why
the
connections
are not
established.

Check to see if
the 1747-SCNR
and the remote
devices are
correctly
connected to
the ControlNet
network.

Module
bandwidth is
exceeded.

Reduce the
number of
scheduled
connections by:
- using a
discrete rack
connection
instead of
multiple
discrete module
connections
- combining
multiple I/O
racks into a
single I/O rack
- combining
multiple
peer-to-peer
messages into
one message.

Increase your
Network Update
Time and/or
increase the
Requested
Packet Intervals
for scheduled
data transfers.

Increase your
SLC 500 ladder
program scan
by adding more
logic.