Select the controlnet node address, Insert the 1747-scnr scanner into the chassis – Rockwell Automation 1747-SCNR SLC ControlNet Scanner Module Installation Instructions User Manual

Page 8

Advertising
background image

8 SLC ControlNet Scanner Module

Publication 1747-IN059C-EN-P - September 2001

Select the ControlNet Node Address

Select the ControlNet node address of the 1747-SCNR by setting the
two 10-digit rotary switches on the top of the scanner. Valid switch
settings range from 01 through 99. Zero (00) is not a valid node
address.

Important:

Since 00 is the default value from manufacturing, you
must change the default value when using the
scanner for the first time.

Insert the 1747-SCNR Scanner Into the Chassis

To insert the 1747-SCNR Scanner into the SLC chassis:

1. Turn off the SLC chassis power supply.

Important:

If you disconnect the ac power, you lose the chassis
ground. Electrostatic damage (ESD) protection is lost.

ATTENTION

ÿ

Do not install the 1747-SCNR Scanner module with
the chassis power supply on. Installing the module
with the chassis power supply on may damage the
module.

Top View of Module

10-digit rotary switches: ones digit

10-digit rotary switches: tens digit

30752