Press, But the force is still enabled, Indicates the force is removed and disabled. the – Rockwell Automation 1747-PT1, D1747NP002 Hand-Held Terminal User Manual
Page 203

Chapter 13
The Force Function
13–5
3. Press [
F2
], OFF. All rungs are false. Program operation is back to the
starting point. The display shows
FORCE OFF
, but the force is still
enabled.
ON OFF REM REM_ALL DISABLE
] [
F RUN
F1
F2
F3
F4
F5
XIC: I1:0.0/1 FORCE OFF 2.0.0.0.1
( )
( )
]/[
] [
]/[
] [
]/[
( )
( )
] [
] [
] [
To disable and/or remove forces, you can select DISABLE, REM, or
REM ALL.
4. Remove the force by pressing [
F3
], REM.
NO FORCE
indicates the force is
removed and disabled. The
F
no longer appears to the left of RUN. The
FORCED I/O LED of the processor is off.
] [
RUN
ON OFF REM REM_ALL ENABLE
F1
F2
F3
F4
F5
XIC: I1:0.0/1 NO FORCE 2.0.0.0.1
( )
( )
]/[
] [
]/[
] [
]/[
( )
( )
] [
] [
] [
5. Press [
ESC
] to exit the force function:
] [
RUN
MODE FORCE EDT DAT SEARCH
F1
F2
F3
F4
F5
XIC: I1:0.0/1 NO FORCE 2.0.0.0.1
( )
( )
]/[
] [
]/[
] [
]/[
( )
( )
] [
] [
] [