Rockwell Automation 1747-PT1, D1747NP002 Hand-Held Terminal User Manual
Page 390

Chapter 27
The Status File
27–22
Fault Classification
Processor
Description
User
Address
Error
Code
(Hex)
I/O Errors
Non-User
Non-Recov
Recov
5/02
5/01,
Fixed
S:6
xx5C
M0–M1 file configuration error – user program M0–M1 file
size exceeds capacity of the module.
X
•
xx5D
Interrupt service requested is not supported by the processor.
X
•
xx5E
Processor I/O driver (software) error.
X
•
xx60 thru
xx6F
Identifies an I/O module specific recoverable major error.
Refer to the user manual supplied with the specialty module.
X
•
xx70 thru
xx7F
Identifies an I/O module specific non-recoverable major error.
Refer to the user manual supplied with the specialty module.
X
•
xx90
Interrupt problem on disabled slot.
X
•
xx91
A disabled slot has faulted.
X
•
xx92
Invalid or non-existent module interrupt subroutine file.
X
•
xx93
Unsupported I/O module specific major error.
X
•
xx94
In the run or test mode, a module has been detected as
being inserted under power. Can also mean that an I/O
module has reset itself.
X
•